Fig. 3 shows a typical installation within a compartment enclosure on the end of a baseboard heater. The back of the compartment enclosure should be equipped with embossing to clear mounting screws. also may be mounted on a wireway (Fig. 4) or junction box. 1. Fasten relay securely to mounting surface using the 2 mounting holes in the or the conduit bushing. 2. Disconnect the power supply. WHEN INSTALLING THIS PRODUCT . . . 1. Read these instructions carefully. Failure to follow them could damag
12. To disconnect the heater, first turn controls to the OFF position, then grip the plug and pull it from the wall outlet. Never pull by the cord. 13. Do not insert or allow foreign objects to enter any ventilation or exhaust opening as this may cause an electric shock or fire, or damage the heater. 14. To prevent a possible fire, do not block air intakes or exhaust in any manner. Do not use on soft surface, like a bed, where openings may become blocked. 15. A heater has hot and arcing or spark
under license from Honeywell Intellectual Properties, Inc. IMPORTANT SAFETY INSTRUCTIONS When using electrical appliances, basic precautionsshould always be followed to reduce the risk of fire, electric shock, and injury to persons, including thefollowing: 1. Read all instructions before using this heater. 2. This heater is hot when in use. To avoid burns, do not let bare skin touch hot surface. If provided, use handles when moving this heater. Keep combustible materials, such as furniture, pill
This warranty does not apply to damage resulting from commercial, abusive, unreasonable use or supplemental damage. Defects that are the result of normal wear and tear will not be considered manufacturing defects under this warranty. KAZ IS NOT LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY NATURE. ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ON THIS PRODUCT IS LIMITED IN DURATION TO THE DURATION OF THIS WARRANTY. Some jurisdictions do not allow the exclusio
TROUBLESHOOTING If your heater shuts off unexpectedly or fails to operate, one of the above-mentioned safety features may have been activated to prevent overheating. • Be sure the power cord is plugged into a working electrical outlet. • Check your Thermostat setting. The unit may simply be off because you have reached your desired heat setting. • Check for any obstructions. If you find an obstruction, turn the heater OFF and unplug it. • Allow the heater to cool completely, then remove the obst
See Fig. 1. SENSING ELEMENT IS FACTORY FORMED FOR 1.5 IN. INSULATION WELL ASSEMBLIES. FOR 3 IN. INSULATION WELL ASSEMBLIES, PULL OUT SUFFICIENT CAPILLARY TO ASSURE THAT THE CAPSULE BOTTOMS IN THE WELL. STRAIGHTEN CAPILLARY SUFFICIENTLY SO IT DOES NOT CAUTION: EXCESSIVE HANDLING OR SHARP BENDS CAN DAMAGE THE CAPILLARY. 2 3 1 2 3 1 INTERFERE WITH INSERTION OF THE CAPSULE INTO THE WELL. M8882 Fig. 1. Adjusting the capillary length. Mounting Each relay is suitable for use with an immersion well for
ASSURE THAT CAPILLARY TUBE FITS FREELY IN THE ADAPTER SO THE TENSION OF THE CAPILLARY TUBE AT POINT (C) HOLDS THE SENSING BULB IN GOOD THERMAL CONTACT WITH THE IMMERSION WELL AT POINT (D 1 1 2 2 (D) (B) (A) L8124A,C,E,L AND M AQUASTAT® RELAYS CONTROLLER CASE IMMERSION WELL CLAMP ADAPTER IMMERSION WELL SPUD BOILER OLD IMMERSION WELL ASSEMBLY BACK OF CONTROLLER CASE IMMERSION WELL CLAMP SCREW ADAPTER SENSING BULB HEAT-CONDUCTIVE COMPOUND SETSCREW CAPILLARY TUBE ) IMMERSION WELL CLAMP IMMERSION SHO
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED. B1 IS 1/4 IN. TAB TERMINAL. M1794A 1 2 3 Fig. 9. L8124E in a 24 Vac, gas-fired, forced hot water, tankless, zoned pump system. 1 TO ADDITIONAL R845A RELAYS L2 L1 FOR OTHER ZONES (HOT) 1 2 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. CONTROL CASE MUST BE CONNECTED TO EARTH GROUND. USE GROUNDING SCREW PROVIDED. 2 1 4 3 5 6 ZONE 1