Par ce dispositif a également d'autres instructions :
Facilité d'utilisation
Rack Installation Instructions
Review the documentation that comes with your rack cabinet for safety and cabling information. When
installing your server in a rack cabinet, consider the following:
v
Ensure the room air temperature is below 35°C (95°F).
v
Install the server only in a rack cabinet that has perforated doors.
v
Do not block any air vents, usually 15 cm (6 in.) of air space provides proper airflow.
v
Plan the device installation starting from the bottom of the rack cabinet.
v
Install the heaviest device in the bottom of the rack cabinet.
v
Do not leave open space above or below an installed server in your rack cabinet. To help prevent
damage to server components, always install a filler panel to cover the open space and to help ensure
proper air circulation.
v
Do not extend more than one device out of the rack cabinet at the same time.
v
Connect all power cords to properly wired and grounded electrical outlets.
v
Do not overload the power outlet when installing multiple devices in the rack.
v
Remove the rack doors and side panels to provide easier access during installation.
v
The slide rails in this kit come preset to the correct length for installation in an IBM rack cabinet and
they are adjustable for other rack cabinets.
v
The slide rails are marked (RIGHT/FRONT and LEFT/FRONT) for proper placement on the
rack-cabinet flanges.
Use safe practices when lifting.
≥18 kg (39.7 lb)
≥32 kg (70.5 lb)
≥55 kg (121.2 lb)
Do not place any object weighing more than
50 kg (110 lb) on top of rack-mounted devices.
≥50 kg (110 lb)
This server does not require any tools for installation, unless you are shipping the server in a rack. When
you are shipping the server in a rack, you will need a Philips screwdriver. The following illustration
shows the items that you need to install the server in a rack cabinet. If any items are missing or
damaged, contact your place of purchase.