|
Facilité d'utilisation
Replacing an existing unit? For details, see the Installation Instructions in this manual. READ AND FOLLOW THIS SAFETY INFORMATION CAREFULLY. SAVE THESE INSTRUCTIONS 2 About the controls on your Zoneline. ge.com TEMP CONTROL MODE CONTROL Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Consumer Support Controls Temp Control The temp control is used to maintain the room temperature. The compressor will cycle on and off to keep the room at the same comfort level. When you turn the knob to COOLER (blue), the indoor air will become cooler. Turn the knob to WARMER (red) and the indoor air will become warmer. 3800 Series only When the outdoor temperature is lower than 20°F, heat is provided by the electric heater in the air conditioner instead of by the heat pump. Mode Control HIGH COOL and LOW COOL provide cooling with different fan speeds. HIGH HEAT and LOW HEAT provide heating with different fan speeds. LOW FAN or HIGH FAN provides air circulation and filtering without cooling or heating. NOTE: If you move the switch from a cool or heat setting to STOP or to a fan setting, the unit has an automatic 3-minute delay before allowing the compressor to restart in the cool or heat mode. About Your Heat Pump (3800 Series only) Heat pumps can save money by removing heat from the outside air—even when the outside temperature is below freezing—and releasing that heat indoors. To get the best performance from your heat pump, don’t change the room thermostat very often. Raising the heat setting 2–3 degrees will cause the Zoneline to use its electric heating elements in order to reach the new temperature setting quickly. There is a three minute minimum compressor run time at any setting to prevent short cycling. The indoor fan motor starts before the compressor and stops after the compressor cycles off. The electric heating elements use much more electricity than heat pumps and cost more to operate. 3 Consumer Support Troubleshooting Tips Care and Cleaning Operating Instructions Safety Instructions Ventilation Control The ventilation control lever is located at the upper left side of the Zoneline unit, behind the room cabinet. When set at the closed position, only the air inside the room is circulated and filtered. When set at the open position, some outdoor air will be drawn into the room. This will reduce the heating or cooling efficiency. Energy Tip: Keep the vent control at the closed position. The room air will be filtered and circulated. NOTE: Two shipping screws must be removed from the vent door before use. See the Installation Instructions in the back of this manual. Air Direction To adjust the air direction, remove the room cabinet. Remove the 7 louver screws that hold the louver insert in place. Flip the louver insert 180°, replace the screws and the room cabinet. Remove the room cabinet and flip the louver insert to change the air direction. 4 Other features of your Zoneline. To Remove the Room Cabinet Additional controls are located behind the room cabinet. To remove: Pull out at the bottom to release it from the tabs (1). Then lift up (2). To replace: Place the tabs over the top rail (1). Push inward at the bottom until it snaps into place (2). Vent control (shown in middle position) Open position Closed position Louver screws Louver screws Auxiliary Controls on your Zoneline. ge.com Auxiliary Controls—Dip Switches The auxiliary dip switch controls are located behind the room cabinet, through an opening in the control panel. Remove the room cabinet. See the To Remove the Room Cabinet section. The factory settings will be in the DOWN position. The owner is responsible for checking switches and ensuring they are in the desired position. Dip Switches Access Cover UP DOWN ALLI2R (All Electric Heat) (3800 Series models only) C: FAN CN (Cooling–Smart Fan) H: FAN CY (Heating–Smart Fan) CLASS 2 (Remote Thermostat) LOAD SHEDDING (CDC) FREEZ Sen (Freeze Sentinel) CONST FAN (Constant ON Fan) OCCUPIED (Occupancy Sensor) UP DOWN HEAT BOOST (3800 Series models only) Heat Sentinel TL1 (H) (Temp. Limit 1–Heat) TL2 (H) (Temp. Limit 2–Heat) TL3 (H) (Temp. Limit 3–Heat) TL1 (C) (Temp. Limit 1–Cool) TL2 (C) (Temp. Limit 2–Cool) TL3 (C) (Temp. Limit 3–Cool) 12345678 12345678 All Electric Heat This electric heat option functions only on the 3800 Series models. When this switch is enabled (UP), heat pump operation is locked out, causing the unit to provide only electric resistance heat. Cooling—Smart Fan When this switch is enabled (UP), it allows the indoor fan to cycle on/off with the compressor. When this switch is disabled (DOWN), it allows the indoor fan to run continuously. Heating—Smart Fan When this switch is enabled (UP), it allows the indoor fan to run continuously. When this switch is disabled (DOWN), it allows the indoor fan to cycle on/off with the heat pump or H: FAN CY (Heating–Smart Fan) heater operation. Safety Instructions Operating Instructions Care and Cleaning Troubleshooting Consumer...
Ce manuel est également adapté pour les modèles :Climatiseurs - 2800 (3.03 mb)