• Allow sufficient space for airflow clearance, wiring, refrigerant piping, and unit servicing. See Fig. 2. • Locate unit so that condenser airflow is unrestricted on all sides and above. Refer to Fig. 2. • Unit may be mounted on a level pad directly on base rails or mounted on raised pads at support points. See Table 2 for weight distribution based on recommended support points. NOTE: If vibration isolators are required for a particular installation, use corner weight information in Table 2 to make proper selection. Table2—Weight Distribution UNIT 38 WEIGHT CHART* Std Unit Corner W Corner X Corner Y Corner Z Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg AK007 340 154 86 39 53 24 77 35 124 56 AK008 370 168 86 39 78 35 99 45 107 49 AK012 395 179 89 40 92 42 109 49 105 48 AKS008 510 231 115 52 89 40 133 60 173 87 AKS009 564 256 133 60 97 44 141 64 193 88 AKS012 564 256 133 60 97 44 141 64 193 88 not unit. If unit is to be skidded into position, place it on a large pad and drag it by the pad. Do not apply any force to unit. Raise from above to lift unit from rails or pad when unit is in final position. After unit is in position, remove all shipping materials and top crating. COMPRESSOR MOUNTING — Compressors are shipped from the factory held down by 4 bolts. After unit is installed, loosen each bolt until the snubber washer can be moved with finger pressure. See Fig. 4. Step 3 — Complete Refrigerant Piping Connections — Suction connection is sweat with plastic cap; liquid connection is sweat with plastic cap. Refer to Table 3A or 3B for the proper line sizes. Follow standard piping practices. SIZE REFRIGERANT LINES — Consider length of piping required between condensing unit and air handler, amount of liquid lift, and compressor oil return. See Table 4A and 4B and also refer to Part 3 of Carrier System Design Manual for design details and line sizing. Refer to air handler installation instructions for additional information. Table 3A — Refrigerant Piping Sizes — 60 Hz LINEAR LENGTH OF PIPING — FT (M) *Weightsareforaluminumcoils. NOTES: 1.Dimensionsin[]areinmillimeters. 2.SeeFig.3foradditionalinformation. Step 2 — Rig and Mount the Unit Be sure unit panels are securely in place prior to rigging. RIGGING — These units are designed for overhead rigging. Refer to rigging label for preferred rigging method. Spreader bars are not required if top crating is left on unit. All panels must be in place when rigging. (See Fig. 3.) As further protection for coil faces, plywood sheets may be placed against sides of unit, behind cables. Run cables to a central suspension point so that angle from the horizontal is not less than 45 degrees. Raise and set unit down carefully. If it is necessary to roll unit into position, mount unit on rails, using a minimum of 3 rollers. Apply force to rails, UNIT 38 0-25 (0-7.6) 25-50 (7.6-15.2) 50-75 (15.2-22.9) 75-100 (22.9-30.5) Line Size (in. OD) L S L S L S L S AK007 1.2 11.8 1.2 11.8 1.2 11.8 1.2 11.8 AK008 1.2 11.8 1.2 11.8 5.8 11.8 5.8 13.8 AK012 5.8 11.8 5.8 13.8 5.8 13.8 5.8 13.8 AKS008 1.2 11.8 1.2 11.8 5.8 11.8 5.8 13.8 AKS009 5.8 11.8 5.8 11.8 5.8 13.8 5.8 13.8 AKS012 5.8 11.8 5.8 11.8 5.8 13.8 5.8 13.8 LEGEND L— Liquid Line S— Suction Line Table 3B — Refrigerant Piping Sizes — 50 Hz LINEAR LENGTH OF PIPING — FT (M) UNIT 38 0-25 (0-7.6) 25-50 (7.6-15.2) 50-75 (15.2-22.9) 75-100 (22.9-30.5) Line Size (in. OD) L S L S L S L S AK007 1.2 11.8 1.2 11.8 1.2 11.8 1.2 11.8 AK008 1.2 11.8 1.2 11.8 5.8 13.8 5.8 13.8 AK012 5.8 11.8 5.8 13.8 5.8 13.8 5.8 13.8 AKS008 1.2 11.8 1.2 11.8 5.8 13.8 5.8 13.8 AKS009 5.8 11.8 5.8 11.8 5.8 13.8 5.8 13.8 AKS012 5.8 11.8 5.8 11.8 5.8 13.8 5.8 13.8 LEGEND L— Liquid Line S— Suction Line NOTES FOR TABLES 3A AND 3B: 1. Pipe sizes are based ona2F(1C) loss for liquid and suction lines. 2. Pipe sizes are based on the maximum linear length shown for each column, plus a 50% allowance for fittings. 3. Charge units with R-22 in accordance with unit installation instructions. 4. Line size conversion to mm is: in. mm 1.2 12.7 5.8 15.9 11.8 28.6 13.8 34.9 4 UNIT 38 DIM. A DIM. B DIM. C DIM. D DIM. E DIM. F AK007 18-61.2. [470.0] 18-23.4. [375.0] — — 18-21.4. [362] 18-45.16. [415] 28-95.16. [846.5] AK008 18-8. [508.0] 18-61.2. [470.0] — — 18-3. [381] 28-5.16. [613] 38-57.16. [1052.5] AK012 18-9. [533.4] 18-8. [508.0] 28-0. [609.6] 18-3. [381] 28-5.16. [613] 38-57.16. [1052.5] AKS008 18-6. [457.2] 18-43.4. [425.5] 28-913.16. [858.8] 18-3. [381] 28-5.16. [613] 38-57.16. [1052.5] AKS009 18-7. [482.6] 18-5. [431.8] 28-913.16. [858.8] 18-3. [381] 28-5.16. [613] 38-57.16. [1052.5] AKS012 18-7. [482.6] 18-5. [431.8] 28-913.16. [858.8] 18-3. [381] 28-5.16. [613] 38-57.16. [1052.5] NOTES: 1. Dimensions in [ ] are in millimeters. 2. Center of Gravity. See chart for dimensions. 3. Direction of Airflow. 4. Minimum clearance (local codes or jurisdiction may ELECTRICAL CONNECTIONS CONNECTION SIZES AA 13.8. Dia [35] Field Power Supply Hole BB 2. Dia [51] Power Supply Knock-out CC 21.2. Dia [64] Pow...

Ce manuel est également adapté pour les modèles :
Séchoirs - 38AK007 (467.2 kb)
Séchoirs - 38AKS008 (467.2 kb)
Séchoirs - 38AKS009 (467.2 kb)
Séchoirs - 38AKS012 (467.2 kb)

Écrivez votre propre critique du dispositif



Texte du message
Votre nom :
Entrez les deux chiffres :
capcha





catégories