Modular System Hardware
Modular Cabinets
• Includes 2 power distribution units (PDU)
° Zero-U rack design
• PDU input characteristics
° 200 to 240 V ac, single phase, 40A RMS, 3-wire
° 50/60Hz
° Non-NEMA Locking CS8265C, 50A input plug
° 6.5 feet (2 m) attached power cord
• PDU output characteristics
° 3 circuit-breaker-protected 20A load segments
° 36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A receptacle
type
° 3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A receptacle type
• Includes front and rear doors
International 380 to 415 V AC input, 3-phase Wye, 16A RMS
Modular Cabinet
• EIA standard 19-inch rack with 42U of rack space
• Geography: International
• Recommended for most configurations
• Includes 2 power distribution units (PDU)
° Zero-U rack design
• PDU input characteristics
° 380 to 415 V ac, 3-phase Wye, 16A RMS, 5-wire
° 50/60Hz
° IEC309 5-pin, 16A input plug
° 6.5 feet (2 m) attached power cord
• PDU output characteristics
° 3 circuit-breaker-protected 16A load segments
° 36 AC receptacles per PDU (12 per segment) - IEC 320 C13 10A receptacle
type
° 3 AC receptacles per PDU (1 per segment) - IEC 320 C19 12A receptacle type
• Includes front and rear doors
International 200 to 240 V AC input, Single phase, 32A RMS
Modular Cabinet
• EIA standard 19-inch rack with 42U of rack space
• Geography: International
• Recommended for most configurations
• Includes 2 power distribution units (PDU)
° Zero-U rack design
• PDU input characteristics
° 200 to 240 V ac, single phase, 32A RMS, 3-wire
° 50/60Hz
° IEC309 3-pin, 32A input plug
° 6.5 feet (2 m) attached power cord
HP Integrity NonStop NS1000 Planning Guide 542527-002