This will be a FAN 1 setting of 75. Set the SS103-10A FAN 2 level 50% higher than FAN 1, or about 112 ppm Set the SS103-3A FAN 2 and the SS103-10A ALARM to 200ppm. Set both Alarm Delays to about 30 minutes. NOTE: Do not set the SS103-10A ALARM higher than 200 ppm when using SS102HC-1 sensors. If the Alarm relay is used to operate a fan, Macurco suggests that the Time Delay be set to about 3 minutes, and on the SS103-10A, the ALARM level be set to 50% higher than the FAN 2 or about 170. ALARM DEL

Macurco SS103-10A

Téléchargements : 4 Taille : 22 kb    Fabricant : Macurco  
Catégorie : Alarme incendie

(If not all zones are used on the SS103-3A &-10A only those appropriate green lights will be on). These SS103 green lights show the sensors are on and in normal operation, and that the wiring between the sensor and control panel is OK. The SS102HC-1 has a 2 1/2 minute warm-up cycle, during which the output voltage progressively increases from 1.0 to 2.1 volts, which will cause the appropriate SS103 zone lights to actuate. Some or all of the Red “SENSOR” lights on the SS103-10A panel may be on at

Macurco SS102HC-1

Téléchargements : 0 Taille : 22 kb    Fabricant : Macurco  
Catégorie : Alarme incendie

The unit is intended to be continuously powered. SENSOR POISONS The gas sensing tip in the detector is designed with extreme sensitivity to the environment. As a result, the sensing function of the tip may be deteriorated if it is exposed to a direct spray from aerosols such as paints, silicone vapors, etc., or to a high density of corrosive gases (such as hydrogen sulfide, sulfur dioxide) for an extended period of time. SERVICING OF UNIT The SS102H & SS102HC-1 do not require regular maintenance

Macurco SS102H

Téléchargements : 13 Taille : 22 kb    Fabricant : Macurco  
Catégorie : Alarme incendie

There is no need to re-calibrate the detectors after installation. The equipment is designed to be fully operational after all wiring is completed. For more technical and wiring information please refer to the Automatic Exhaust Fan Controllers For Parking Garages & Carbon Monoxide Transducers data sheets. LOCATION Please refer to the attached data sheet titled “Carbon Monoxide System Layouts in Parking Garages” SS102H & SS102HC-1 GENERAL INFORMATION The SS102H is partially housed in a plastic ca

Macurco DVP-120

Téléchargements : 4 Taille : 463 kb    Fabricant : Macurco  
Catégorie : Alarme incendie

5 1.2 Features .............................................................................................................................................. 5 1.3 Compatible Macurco Transducers...................................................................................................... 5 1.4 Specifications ..................................................................................................................................... 8 1.5 Warranty..................................

Macurco CM-S1

Téléchargements : 4 Taille : 71 kb    Fabricant : Macurco  
Catégorie : Alarme incendie

NOTE: Any time the words “Control Panel” or “Alarm Panel” or “Alarm Control Panel” are used in these instructions, what is meant is a UL Listed Fire or Fire/Burglar or Critical Process Management Equipment. Alarm control panels that work on 12 or 24 VDC can provide battery backup to the CM-S1 detectors. This carbon monoxide detector is designed to detect CO gas from ANY source of combustion. It is NOT designed to detect smoke, fire or any other gas. LOCATION There are two usual sources of CO in